DA561 (Discontinued)

Isolation Transmitter for mA/V Signals with 2-wire Transmitter Supply

DA561 is specially designed for signal isolation and load amplification in the process industry.
A 2-wire transmitter can be connected to and supplied from the isolation amplifier. DA561 maintains a high isolation level (1,5 kV) between input and output. Current and voltage can be chosen independently as input and output signals.

  • Current and voltage input
  • Current and voltage output
  • Direct connection of 2-wire transmitter
  • Output test terminals
  • 1 500 V isolation level
  • Short response time
  • High noise immunity
  • Available for AC or DC power supply
  • DIN-rail mounting
  • Plug-in screw terminals
Category: .

Technical Specification

Input Voltage  0(0,2)-1 V, 0(1)-5 V, 0(2)-10 V
Input impedance 1 MΩ
Input Current 0(4)-20 mA (standard setting)
Input impedance 11,9 Ω
Maximum input level 200 % of measurement span
Output Voltage 0(0,2)-1 V, 0(1)-5 V, 0(2)-10 V, short circuit protected
Minimum load 500 kΩ (error effect
Voltage limitation Approx. 56 V
Output Current 0(4)-20 mA, open or short circuit protected
(standard setting)
Maximum load 600 Ω
Current limitation Approx. 23 mA
Test output mA instrument, Ri ≤ 10 Ω
Transmitter supply voltage 19 VDC, max. ripple 100 mV p-p
Operation temperature -20 to +60 °C / -4 to +140 °F
Galvanic isolation AC & DC version
Input to output 1 500 VAC, 1 min
Input/output to power supply 2 200 VAC, 1 min
Power supply AC versions 230 VAC, -15..+10 %, 45..75 Hz,
115 VAC, -15..+10 %, 45..75 Hz
Power supply DC version 19 to 60 VDC
Typical accuracy ±0,15 % of span
Connections Plug-in terminals Stranded, ≤ 2.5 mm2, AWG 14
Mounting Rail acc. to DIN EN 50022, 35 mm

Request a quote